Power and Interface Switching Module ConTrace IPS

Power and Interface Switching Module ConTrace IPS

Features

  • Power and interface switching RS-485 for 40 MS modules
  • Networking for 247 MS, AS, and AS-xxx-Ex Units
  • Automatic switching from primary to redundant power supplies
Product Datasheet

Approvals

The ConTrace IPS module, depending on the number of MS modules connected to it, is connected to the power units of the appropriate power, as well as to the RS-485 network, for communication with the industrial PC / PLC. Further, through the patch cord, it simultaneously transmits power and interface to the ConTrace MS modules. Further, through the patch cord, it simultaneously transmits power and interface to the ConTrace MS modules. IPS has 2 outputs, combining power and interface buses. For each output, up to 20 MS modules can be connected in series. Thus, with the help of one IPS, it is possible to power up to 40 MS modules.

ConTrace IPS can work from either one or two power supplies. Operation from two power sources is assumed by the principle of primary / backup, with automatic switching to a working power supply and simultaneous signaling by closing the alarm relay contact. The IPS module is protected against excess supply voltage.

Each of the two output power and interface lines is equipped with its own protection against overcurrent, undervoltage and overvoltage. The operation of the protection is indicated by the LEDs on the front panel. Resetting the protection is done by pressing the “Reset” buttons on the device, separately for each outgoing line.

ConTrace IPS is supplied with three terminators of the ConTrace BT bus. This set is sufficient for implementing any connection scheme.

  • Power and interface switching RS-485 for 40 MS modules
  • Networking for 247 MS, AS, and AS-xxx-Ex Units
  • Automatic switching from primary to redundant power supplies
  • Indication and notification of alarms
  • Protection of incoming and outgoing circuits
Technical Data
Module supply voltage 20...30 V
Power consumption, max 3W
Maximum number of MS modules 40 pcs*
Maximum number of MS modules in one RS-485 network segment 247 pcs
Maximum number of IPS modules in one RS-485 network segment without a repeater 32 pcs
Type of connectors RS-485+24 и RS-485 8P8C
Type of connection cable RS-485+24 и RS-485 UTP/FTP cat.5
Data transfer interface RS-485
Built-in RS-485 signal repeater Yes
The maximum current of each output line 3 A
Maximum allowable current for each output line 5 A

* taking into account the connected redundant modules in the “1 + 1” scheme