Capillary Thermostat heatTHERM-AT

Capillary Thermostat heatTHERM-AT
−30°C
+80°C

Features

  • Stable switching point position due to ambient temperature compensation (standard)
  • Max. switching capacity 16 A, 230 V
  • Tested according to DIN EN 14597
Product Datasheet

Application Areas

Freeze protection of pipelines and vessels

Approvals

Capillary Thermostat heatTHERM-ATCapillary Thermostat heatTHERM-ATCapillary Thermostat heatTHERM-AT

The capillary thermostat heatTHERM-AT can be used to control electrical heating systems for freeze protection of pipelines and vessels. The thermostat controls the electrical heating system according to the ambient temperature.

The heatTHERM-AT is a temperature monitor (TW). When the temperature of the sensing element falls below the setting point, the micro switch trips the transmission mechanism and the power circuit closes. At the same time, the signal circuit is opened. If the temperature of the sensing element exceeds the set value (switching differential), the microswitch trips, the power circuit is opened. The signal circuit, in turn, closes.

  • Stable switching point position due to ambient temperature compensation (standard)
  • Max. switching capacity 16 A, 230 V
  • Tested according to DIN EN 14597
  • Operating life at least 250,000 switching cycles
  • Switching point deviation during the entire operating life of up to ± 5 %
  • Protection type IP54
Technical Data
Temperature setting range −10 ... +40 °C
Max. switching capacity contact deck 1-2
AC 230 V +10%, 16 (2.5) A, cos φ = 1 (0.6)
contact deck 1-4
AC 230 V +10 %, 2 (04) A, cos φ = 1 (0.6)
Hysteresis Approx. 2.5 %
Protection type IP54
Weight Approx. 200 g
Cable inlet Cable gland M20×1.5, for cable ø6-12 mm
Ambient temperature range −30 ... +80 °C
Diameter of probe 17 mm coiled probe
Capillary material Stainless steel (CrNi)
Dimension:
Without cable glands and probe
Included cable glands and probe
120×53×58 mm
160×80×58 mm
Installation type Surface mounted